Учебное пособие к курсовому и дипломному проектированию строительных процессов при возведении подземной части здания


Measures for water drainage and artificial lowering of groundwater



бет26/62
Дата31.12.2021
өлшемі12,75 Mb.
#22189
түріУчебное пособие
1   ...   22   23   24   25   26   27   28   29   ...   62
9. Measures for water drainage and artificial lowering of groundwater

During implementation of zero cycle construction works it is necessary that the bottom of the pit (trench) was cleaned from groundwater. For this purpose, is used an open drainage, artificial lowering of groundwater levels and other ways.

The choice of method for groundwater control depends on the nature of the soil and excavation depth. Recommendations for choose of drainage and dewatering systems depends on the soil type that can be accepted from [2].

Open drainage is produced by pumping units, while entering the pit (trench) water is collected in areaway (shaft bottom sump), from there it is swap out by pump in the open or underground drains.


With an open dewatering can be assumed that 1 м2 of pit (trench) surface and vertical projections of the walls, locations below the static groundwater level, the water flow is:

-при мелкозернистых песках 0,16;

-при среднезернистых песках 0,24;

-при круннозернистых песках 0,3– 3,0;

-при трещиневатых скалистых погодах 0,15–0,5м3/ч.


Поступление воды в котлован (траншею) в м3/ч можно определить по формуле:
𝑄 = (𝐹дна + 𝐹отк.) ∙ 𝛼,

где, 𝐹дна (к),(тр) – площадь дна, котлована (траншеи), м2;



𝐹дна к = 𝑙1п.н𝑙2п.н,

𝐹дна тр.= 𝐿 𝑙2п.н,

𝐹отк. – площадь откосов, расположенных ниже уровня грунтовых вод, м2;



𝐹отк.к= (ℎ𝑘 угв) Рк

𝐹отк.тр= (ℎтр угв) 𝐿

𝑘, ℎтр глубина котлована или траншеи (по заданию);

угв уровень грунтовых вод (по заданию);



Рк периметр котлована (𝑙1 + 𝑙2) ∙

2;

𝐿– длина траншеи;



𝛼 – приток воды с 1м2, 0,16– 0,5м3/ч.;

Количество насосов необходимых для откачки воды:


𝑁 = 𝑄∙𝐾3,

Пн


где, 𝐾3 – коэффициент запаса, принимается равным 1,1–1,2;

Пнчасовая производительность



-with fine–grained sands 0,16;

-with medium–grained sands 0,24;

-with coarse sands 0,3–3,0;
-with fracture rock material 0,15– 0,5𝑚3/h.
Water inflow into the pit (trench) in m3/h can be calculated by the formula:
𝑄 = (𝐹𝑎.𝑏(𝑡𝑟) + 𝐹𝑠𝑙.) 𝛼

where, 𝐹𝑎.𝑏 (𝑝),(𝑡𝑟)– area of a bottom, pit (trench), 𝑚3



𝐹𝑎.𝑏.(𝑝) = 𝑙1𝑠.𝑏𝑙2𝑠.𝑏,

𝐹𝑎.𝑏(𝑡𝑟) 𝐿 ∙ 𝑙2𝑠.𝑏,

𝐹𝑠𝑙. – slope area, located below the groundwater level, 𝑚2


𝐹𝑠𝑙.= ( ℎ𝑝 − ℎ𝑔𝑤𝑙) ∙ Р𝑝

𝐹𝑠𝑙.= (ℎ𝑡𝑟 − ℎ𝑔𝑤𝑙) ∙ 𝐿
𝑝, ℎ𝑡𝑟 pit or trench depth (per the task);

𝑔𝑤𝑙 – level of underground water, m

(per the task);



Р𝑝 perimeter of the pit (𝑙1 + 𝑙2) ∙ 2 ;
𝐿– trench length;

𝛼 – water inflow from 1𝑚2, 0,16 – 0,5𝑚3/h.;

The number of pumps required for water pumping:
𝑁 = 𝑄∙𝑆𝑓,

𝑃𝑛


where, 𝑆𝑓– assurance coefficient, to be taken to be equal to 1,1–1,2;

𝑃𝑛– hour pump capacity, (annex. №1.






насоса, (прилож. №1. табл.8) м3/ч.
При значительном притоке грунтовых вод ( в грунтах с коэффициентом фильтрации от 2 до

40 м/сут.), рекомендуется использовать метод искусственного понижения грунтовых вод с применением иглофильтровых установок, которые располагаются по внешнему периметру земляного сооружения на расстоянии 0,5–1м от кромки откоса котлована (траншеи).

Приток воды к замкнутым установкам для котлованов подсчитывается по формуле:
𝑄 = 𝛼 ∙ 𝐾 ∙ 𝑆,
где, 𝑄 – приток воды, м3/ч;

𝛼 – коэффициент, изменяющийся в пределах от 1 до 3м;

𝐾 – коэффициент фильтрации (для глины – 0,005; суглинка – 0,005–0,4; супесей – 0,2–0,7; песка мелкого – 1–10; песка среднего – 10–25; песка

крупного – 25–75; гравия – 75–1000 м/сут);